Module 16 - Introduction to Test Equipment
Navy Electricity and Electronics Training Series (NEETS)
Chapter 3:  Pages 3-11 through 3-20

Module 16 − Introduction to Test Equipment

Pages i, 1−1, 1−11, 1−21, 2−1, 2−11, 2−21, 3−1, 3−11, 3−21, 3−31, 4−1, 4−11, 4−21, 5−1, 5−11, 5−21, 5−31, 6−1, 6−11, 6−21, 6−31, 6−41, Index

 

 

portion of it) directly to the meter terminals. The resulting excessive current burns up the meter coil and renders the meter useless until repaired.

 

Q-11.   In what manner are current-measuring instruments connected to a circuit?

 

If you do not know the approximate value of current in the circuit, you should take a reading at the highest range of the ammeter; then you should switch progressively to lower ranges until a suitable reading is obtained. Most ammeter scales indicate the current being measured in increasing values from left to right. If you connect the meter without observing proper polarity, the pointer may be deflected backwards (from right to left). This action often damages the meter movement. You should ensure that the ammeter is always connected so that the current will flow into the negative terminal and out the positive terminal. Figure 3-6 shows various circuit arrangements and the proper ammeter connection methods to measure current in various portions of the circuit.

 

Proper ammeter connection - RF Cafe

Figure 3-6. - Proper ammeter connection.

 

Q-12.   An ammeter should always be connected so that current will flow into what terminal and out of what terminal?

 

Ammeter Sensitivity

 

Ammeter sensitivity is determined by the amount of current required by the meter coil to produce full-scale deflection of the pointer. The smaller the amount of current required to produce this deflection, the greater the sensitivity of the meter. a meter movement that requires only 100 microamperes for full- scale deflection has a greater sensitivity than a meter movement that requires 1 milliampere for the same deflection.

 

Q-13.   (True or False) The larger the current required to produce full-scale deflection of the meter coil, the better the sensitivity of the meter.

 

Good sensitivity is especially important in ammeters to be used in circuits in which small currents flow. As the meter is connected in series with the load, the current flows through the meter. If the internal resistance of the meter is a large portion of the load resistance, an effect known as METER-LoadING will occur. Meter-loading is the condition that exists when the insertion of a meter into a circuit changes the operation of that circuit. This condition is not desirable. The purpose of inserting a meter into a circuit is to allow the measurement of circuit current in the normal operating condition. If the meter changes the

 

 

3-11

circuit operation and changes the amount of current flow, the reading you obtain will be in error. An example of this is shown in figure 3-7.

 

Ammeter loading effect - RF Cafe

Figure 3-7. - Ammeter loading effect.

 

Q-14.   What condition exists when the insertion of a meter into a circuit changes the operation of the circuit?

 

In view a of figure 3-7, the circuit to be tested has an applied voltage of 100 millivolts and a resistance of 100 ohms. The current normally flowing in this circuit is 1 milliampere. In view B, an ammeter that requires 1 milliampere for full-scale deflection and that has an internal resistance of 100 ohms has been inserted. Since 1 milliampere of current flow is shown in view A, you might naturally assume that with the meter inserted into the circuit, a full-scale deflection will occur. You might also assume that the 1 milliampere of circuit current will be measured. However, neither of these assumptions is correct. With the ammeter inserted into the circuit, as shown in view B, the total resistance of the circuit is 200 ohms. With an applied voltage of 100 millivolts, applying Ohm's law shows the actual current (Icircuit) to be 0.5 milliampere.

 

Equation - RF Cafe

 

 

 

Since the meter reads 0.5 milliampere instead of the normal value of current, the meter reveals that a definite loading effect has taken place. In cases such as this, the use of ammeters, which have a lower internal resistance and a better current sensitivity, is desirable.

 

DC VOLTMETER

 

Up to this point, we have been discussing the 100-microampere D'Arsonval movement and its use as an ammeter. However, it can also be used to measure voltage if a MULTIPLIER (high resistance) is placed in series with the moving coil of the meter. For low-voltage instruments, this resistance is physically mounted inside the meter case with the D'Arsonval movement. The series resistance is constructed of a wire-wound resistance that has a low temperature coefficient wound on either a spool or

 

 

3-12

card frame. For high-voltage ranges, the series resistance can be connected externally. a simplified diagram of a voltmeter is shown in figure 3-8.

 

Internal construction and circuit of a simplified voltmeter - RF Cafe

Figure 3-8. - Internal construction and circuit of a simplified voltmeter.

 

Q-15.   What modification is made to the D'Arsonval meter movement to enable the meter to measure voltage?

Keep in mind that the D'Arsonval meter movement uses current flow to produce a magnetic field that is proportional to the current. The meter movement is, therefore, an indicator of current flow rather than voltage. The addition of the series resistance is what allows the meter to be calibrated in terms of voltage; that is, the meter movement of a voltmeter operates because of the current flow through the meter, but the scale is marked in volts. For example, the meter movement shown in figure 3-9 has an internal resistance of 100 ohms, requires 100 microamperes for full-scale deflection, and has a voltage drop of 10 millivolts when full-scale deflection is reached. If you were to place this meter directly across a 10-volt source, an excessive current (in milliamperes) would flow. The meter would be destroyed because of the excessive current flowing through the meter movement. This can be seen in the following Ohm's law application:

 

Use of multiplier resistors with D'Arsonval meter movement - RF Cafe

Figure 3-9. - use of multiplier resistors with D'Arsonval meter movement.

 

Using this equation, you can see that a current through the meter of 100 milliamperes is excessive and will cause damage.

 

 

3-13

 

Equation - RF Cafe

 

Since the normal voltage drop for the meter is 10 millivolts at full-scale deflection, some means must be supplied to drop the extra 9.99 volts without applying it directly to the meter. This is done by the addition of a multiplier resistor, as shown in figure 3-9.

 

Extending Voltmeter Ranges

 

The value of series resistance is determined by the current required for full-scale deflection and by the range of the voltages to be measured. Since the current through the meter circuit is directly proportional to the applied voltage, the meter scale can be calibrated directly in volts for a fixed value of series resistance. For example, let's assume that the basic meter is to be made into a voltmeter with a full- scale deflection of 1 volt. The coil resistance of the basic meter is 100 ohms, and 100 microamperes of current causes full-scale deflection.  The resistance (Rmeter) required to limit the total current in the circuit to 100 microamperes can be found as follows:

 

Equation - RF Cafe

 

Because the meter coil already measures 100 ohms, the series resistance required is equal to 10 kilohms minus 100 ohms, or 9.9 kilohms.

 

Q-16.   What factors determine the value of the multiplier resistor?

 

Multirange voltmeters use one meter movement. The required resistances are connected in series with the meter by a switching arrangement. a schematic diagram of a multirange voltmeter with three ranges is shown in figure 3-10.  The total meter resistance (Rmeter) for each of the three ranges, beginning with the 1-volt range, is figured by the application of Ohm's law, as follows:

 

 

3-14

 

Formula - RF Cafe

 

 

Multirange voltmeter - RF Cafe

Figure 3-10. - Multirange voltmeter.

 

The actual value of the multiplying series resistor (Rseries) for each of these circuits is 100 ohms less than the total resistance. This allows for the resistance of the meter coil (Rcoil).

 

Voltmeter Circuit Connections

 

When voltmeters are used, a primary rule of safety is that such voltage-measuring instruments must always be connected  in parallel with (across) a circuit. If you are unsure of the level of the voltage to be measured, take a reading at the highest range of the voltmeter and progressively (step by step) lower the range until a suitable reading is obtained. In many cases, the voltmeter you will be using will not be a

 

 

3-15

center-zero- (0 reading is in the center) indicating instrument. Observing the correct polarity is important when connecting the instrument to the circuit. Voltmeter polarity is the same as for the dc ammeter; that is, current flows from negative to positive.

 

Q-17.   In what manner are voltage-measuring instruments connected to the circuit to be measured?

 

Influence of a Voltmeter in a Circuit

 

The purpose of a voltmeter is to indicate the potential difference between two points in a circuit. When a voltmeter is connected across a circuit, it shunts the circuit. If the voltmeter has a low resistance, it will draw a substantial amount of current. This action lowers the effective resistance of the circuit and changes the voltage reading. When you are making voltage measurements in high-resistance circuits, use a High-Resistance VOLTMETER to prevent the shunting action of the voltmeter. The effect is less noticeable in low-resistance circuits because the shunting effect is less. The problem of voltmeter shunting (sometimes called circuit loading) is illustrated in figure 3-11.

 

Shunting action caused by a voltmeter - RF Cafe

Figure 3-11. - Shunting action caused by a voltmeter.

 

Q-18.   When making voltage measurements in a high-resistance circuit, you should always use a voltmeter with what relative value of resistance?

 

In view a of figure 3-11, a source of 150 volts is applied to a series circuit consisting of two 10- kilohm resistors. View a shows the voltage drop across each resistor to be 75 volts. In the 150-volt range, the voltmeter to be used has a total internal resistance of 10 kilohms. View B shows the voltmeter connected across the circuit. The parallel combination of R2 and the meter now present a total resistance of 5 kilohms. Because of the addition of the voltmeter, the voltage drops change to 100 volts across R1 and 50 volts across R2. Notice that this is not the normal voltage drop across R2. Actual circuit conditions have been altered because of the voltmeter.

 

Voltmeter Sensitivity

 

The sensitivity of a voltmeter is given in ohms per volt. It is determined by dividing the sum of the resistance of the meter (Rmeter), plus the series resistance (Rseries), by the full-scale reading in volts. In equation form, sensitivity is expressed as follows:

 

Equation - RF Cafe

 

This is the same as saying the sensitivity is equal to the reciprocal of the full-scale deflection current. In equation form, this is expressed as follows:

 

 

3-16

 

Equation - RF Cafe

 

Therefore, the sensitivity of a 100-microampere movement is the reciprocal of 0.0001 ampere, or

10,000 ohms per volt.

 

Equation - RF Cafe

 

Q-19.   What term is used to express the sensitivity of a voltmeter?

 

METERS useD for MEASURING Resistance

 

The two instruments you will use most often to check continuity, or to measure the resistance of a circuit or circuit component, are the OHMMETER and the MEGGER (MEGOHMMETER). The ohmmeter is widely used to measure resistance and to check the continuity of electrical circuits and devices. Its range usually extends to only a few megohms. The megger is widely used for measuring insulation resistance, such as that between a wire and the outer surface of its insulation, and the insulation resistance of cables and insulators. The range of a megger can be extended to more than 1,000 megohms.

 

Q-20.   What instrument is used for measuring the insulation resistance of cables?

 

The Ohmmeter

 

A simple ohmmeter circuit is shown in figure 3-12. The ohmmeter consists of the dc milliammeter, discussed earlier in this chapter, and the added features shown below:

 

 

3-17

 

Simple ohmmeter circuit - RF Cafe

Figure 3-12. - Simple ohmmeter circuit.

 

· a source of dc potential; and

·  One or more resistors (one of which is variable).

 

Q-21.   What added features enable a dc milliammeter to function as an ohmmeter?

 

The deflection of the pointer of an ohmmeter is controlled by the amount of battery current passing through the moving coil. Before you can measure the resistance of an unknown resistor or electrical circuit, you must calibrate the ohmmeter to be used. If the value of resistance to be measured can be estimated within reasonable limits, select a range on the ohmmeter that will give approximately half-scale deflection when the resistance is inserted between the probes. If you cannot estimate the resistance to be measured, then set the range switch on the highest scale. Whatever range you select, the meter must be calibrated to read zero before the unknown resistance is measured.

 

To calibrate the meter, you first short the test leads together, as shown in figure 3-12. With the test leads shorted, a complete series circuit exists. The complete series circuit consists of the 3-volt source, the resistance of the meter coil  (Rmeter), the resistance of the zero-adjust rheostat, and the series multiplying resistor (Rseries). The shorted test leads cause current to flow and the meter pointer to deflect.

 

Notice that the zero point on the ohmmeter scale (as opposed to the zero points for voltage and current) is located at the extreme right side of the scale. With the test leads shorted, the zero-adjust potentiometer is set so that the pointer rests on the zero mark. Therefore, a full-scale deflection indicates zero resistance between the leads.

 

Q-22.   a full-scale deflection on an ohmmeter scale indicates what resistance between the leads?

 

If you change the range on the meter, you must "zero" (calibrate) the meter again to obtain an accurate reading. When you separate the test leads, the pointer of the meter will return to the left side of the scale. This action, as explained earlier, is caused by the restoring force of the spring tension acting on the movable coil assembly. The reading at the left side of the scale indicates an infinite resistance.

 

3-18

After you have adjusted the ohmmeter for zero reading, it is ready to be connected to a circuit to measure resistance. a typical circuit and ohmmeter arrangement is shown in figure 3-13. You must ensure that the power switch of the circuit to be measured is in the de-energized (ofF) position. This prevents the source voltage of the circuit from being applied to the meter, a condition that could cause severe damage to the meter movement.

 

Measuring circuit resistance with an ohmmeter - RF Cafe

Figure 3-13. - Measuring circuit resistance with an ohmmeter.

 

Remember that the ohmmeter is an open circuit when the test leads are separated. To take a resistance reading with a meter, you must provide a path for current flow produced by the meter's battery. In view a of figure 3-13, the meter is connected at points a and B to produce this path. Connecting these test leads places resistors R1 and R2 in series with the resistance of the meter coil, the zero-adjust potentiometer, and the series multiplying resistor. Since you previously calibrated the meter, the amount of coil movement now depends only on the resistances of R1 and R2.

 

The addition of R1 and R2 into the meter circuit raises the total series resistance and decreases the current. This decreases the amount of pointer deflection. The pointer comes to rest at a scale reading that indicates the combined resistance of R1 and R2. If you were to replace either R1 or R2, or both, with a resistor having a larger ohmic value, the current flow in the moving coil of the meter would be decreased even more. This would further decrease the pointer deflection, and the scale indication would read a still higher circuit resistance. View B is a simplified version of the circuitry in view A.

 

From our ohmmeter discussion, two facts should be apparent: (1) Movement of the moving coil is proportional to the amount of current flow, and (2) the scale reading of the ohmmeter is inversely proportional to current flow in the moving coil.

 

The amount of circuit resistance to be measured may vary over a wide range. In some cases, it may only be a few ohms; in other cases, it may be as great as 1 megohm. Scale multiplication features are built into most ohmmeters so that they will indicate any ohmic value being measured and offer the least amount of error. Most ohmmeters are equipped with a selector switch for selecting the multiplication scale desired. For example, view a of figure 3-14 shows a typical meter that has a six-position switch. The positions are marked on the meter in multiples of 10, from R x 1 through R x 100K.

 

 

3-19

 

Ohmmeter with multiplication switch - RF Cafe

Figure 3-14. - Ohmmeter with multiplication switch.

 

The range used to measure any particular unknown resistance (Rx  in view a of figure 3-14) depends on the approximate ohmic value of the unknown resistance. For instance, the ohmmeter scale of the figure is calibrated in divisions from 0 to infinity. Note that the divisions are easier to read on the right-hand portion of the scale than on the left. For this reason, if Rx  is greater than 1,000 ohms and if you are using the R x 1 range, you will be unable to accurately read the indicated resistance. This happens because the combined series resistance of resistors Rx  is too large for range R x 1 to allow enough battery current to flow to deflect the pointer away from infinity. You need to turn the range switch to the R x 10 position to obtain the 1,000-ohm reading.

 

Let's assume that you have changed the range switch to the R x 10 position and the pointer now deflects to a reading of 375 ohms, as shown in view B of figure 3-14. This would indicate to you that unknown resistance Rx  has 3,750 (375 times 10) ohms of resistance. The change of range caused the deflection because resistor R x 10 has only 1/10 the resistance of resistor R x 1. Therefore, selecting the smaller series resistance allowed a battery current of sufficient value to cause a readable pointer deflection. If the R x 100 range were used to measure the same 3,750 ohm resistor, the pointer would deflect still further to the 37.5-ohm position, as shown in view C. This increased deflection would occur because resistor R x 100 has only 1/10 the resistance of resistor R x 10.

 

Q-23.   The R x 100 resistance selection on an ohmmeter has what amount of resistance compared to the R x 10 selection?  The circuit arrangement in view a of figure 3-14 allows the same amount of current to flow through the moving meter coil. The same amount is allowed to flow whether the meter measures 10,000 ohms on the R x 1 scale, 100,000 ohms on the R x 10 scale, or 1,000,000 ohms on the R x 100 scale.

 

 

3-20

NEETS Modules
- Matter, Energy, and Direct Current
- Alternating Current and Transformers
- Circuit Protection, Control, and Measurement
- Electrical Conductors, Wiring Techniques, and Schematic Reading
- Generators and Motors
- Electronic Emission, Tubes, and Power Supplies
- Solid-State Devices and Power Supplies
- Amplifiers
- Wave-Generation and Wave-Shaping Circuits
- Wave Propagation, Transmission Lines, and Antennas
- Microwave Principles
- Modulation Principles
- Introduction to Number Systems and Logic Circuits
- - Introduction to Microelectronics
- Principles of Synchros, Servos, and Gyros
- Introduction to Test Equipment
- Radio-Frequency Communications Principles
- Radar Principles
- The Technician's Handbook, Master Glossary
- Test Methods and Practices
- Introduction to Digital Computers
- Magnetic Recording
- Introduction to Fiber Optics
Note: Navy Electricity and Electronics Training Series (NEETS) content is U.S. Navy property in the public domain.